Your project, unchanged
Every CPU of the project runs as a simulator, started from BlueEdit with one menu command – with the configuration and programs you upload to the plant.
Software
Full system simulation on a PC – test, demonstrate and train without controllers or I/O cards.
BlueSimul runs the systems of a BlueEdit project on a Windows PC. Each controller becomes a simulator that runs the BlueDaemon4 runtime with the unmodified application programs. Around the simulators, BlueSimul simulates the I/O cards, the communication partners and, with a process model, the plant.
GA BlueEdit and GA TurWin connect to the simulators just as they connect to the controllers on site.
What BlueSimul gives you in day-to-day project work – each shown below with screenshots of real plant projects.
Every CPU of the project runs as a simulator, started from BlueEdit with one menu command – with the configuration and programs you upload to the plant.
Live view of the rack, state, I/O, services, connections, tasks and syslog of every simulator.
Inputs in engineering units, function generators with eleven waveforms that run in step across units, and trends with cursors and reference runs.
Card, channel, MCU, self-test, board voltage, CPU, network, power supply and fan faults – the simulated hardware reacts as its firmware does.
Duplex, TMR, horizontal CPU pairs and MPU-M1: leading unit, tracking, switchover and settling behave as on the plant.
Every field signal of the project, wired to every unit, with per-unit offsets, presets and a test record for the factory acceptance test (FAT).
Save the state of a test under a name, load it again, compare it with the running simulation and pass it on to a colleague.
BlueSimul Communication simulates the Modbus TCP, Modbus RTU and LAN partners that the programs address, without any configuration.
The plant as a Python script, with an editor that knows the project, a dry run, an online debugger and a live model window.
Open the project in BlueEdit, switch on Loopback mode and choose Simulation > Start CPU simulator. BlueSimul Control opens with the project and draws every rack as BlueEdit’s rack configurator places it: the CPUs, the I/O cards with their LEDs, the switches, power supplies and key switches. Click Start, and the whole project comes to life.
Each simulator has a status window that shows what a technician would like to see on a real controller. A colored header per unit shows at a glance whether it is running, in maintenance or not answering, the leading unit, tracking, missing partners and the alerts of the last two minutes.
A click on a digital input switches it; a click on an analog input opens a slider and a list of values that exercise the range checks. With Physical units a channel appears in engineering units, such as 50.0 barg or 3515 rpm, while the card receives mA or Hz.
A generator drives an input along a defined curve, without a process model: a ramp through 4–20 mA to check limit trips and their hysteresis, a staircase for a loop check, a sine wave for a filter. Eleven waveforms are available, up to a table of up to 1000 points loaded from a CSV file. Sync groups let generators on different units run in step or with a fixed phase shift, which trips a deviation alarm deliberately and at the same moment in every run.
Inputs can carry the disturbances of a real plant: card noise including component tolerances, transmitter noise, 50 Hz mains hum, bursts, loose contacts, contact bounce and bus faults. Up to 16 channels per simulator are sampled every 100 ms and kept for 30 minutes – with zoom, two cursors, CSV export and a reference run shown as dashed curves.
BlueSimul injects the faults of real hardware, and the simulated card or CPU reacts as its firmware does: it reports the fault to the program, to BlueEdit and to the syslog, and switches the outputs off where the firmware does. The application sees the fault as it would on the plant, which makes BlueSimul the right place to test diagnostics and fault reactions.
Every fault is written to the syslog and saved with a scenario, and all faults except a halted application persist across a restart. With Blinking LEDs switched on, the rack shows the code of a fault reaction on the LEDs of the MCU, as the real card does.
| Where | Faults |
|---|---|
| Cards | Card pulled, MCU-A or MCU-B failed, bus faults |
| Channels | Open circuit, short circuit, underrange, overrange, channel fault, deviation of an output current; a detected fault is latched until an error reset, as on the real card |
| MCU-S firmware | Fault reactions A, B, C, D and G, every self-test and power-on test, board voltages and temperature out of tolerance, the 24 V supply of an MCDOT-S |
| CPU | Every warning and error bit of the SYS block, failure of one or all networks, halted application |
| Rack | Power supply 1 or 2 failed, cooling fan failed |
The simulators of a duplex or TMR system exchange their data over the simulated networks as the controllers do: they choose the leading unit, track each other and take over when a unit fails. The hot-standby output cards decide among themselves which card drives the outputs. This lets you test the redundancy of an application on the PC, including the behavior of the HMI and the Modbus masters during a switchover.
| To test | Do this in BlueSimul Control |
|---|---|
| Failure of the leading unit | Click Stop in the header of the leading unit |
| Failure of the leading-slot card | Pull the card in the leading slot |
| Program that does not run | Choose Application halted in the menu of the unit |
| Network failure | Fail one network of the unit, or all of them |
| Failed MCU of an output card | Choose MCU-A failed or MCU-B failed in the menu of the card |
Before commissioning, a project is tested on a test rack: a potentiometer for every transmitter, a switch for every contact, a lamp for every output. The virtual test rack simulates this panel. It knows the field signals of the project and how each one is wired to the cards of the units: one value set for a transmitter reaches every card input it is wired to, on every unit of the system.
It does what a physical rack cannot:
A test session builds up state: cards pulled, faults injected, inputs set, generators running, key switches turned, signals forced from BlueEdit. A scenario saves all of this under a name for every simulator of the project, on request including the forces and the uploaded programs. Loading a scenario takes effect on the running simulators without a restart.
Typical uses are a clean starting point before each test, the same fault pattern for every run, a quick way back after a program change, and prepared exercises for training.
Devices outside the project, such as a DCS, an overspeed protection unit, a vibration monitor, a managed switch or a neighboring plant, are simulated by BlueSimul Communication. It derives them from the programs on the simulators and therefore needs no configuration of its own: Modbus TCP servers and clients, Modbus RTU slaves and masters, SoE clients and the partners of LAN messages.
Without a plant, every input holds the value that was last set. That is enough to test a trip or an interlock, but not a control loop. A process model closes the loop: a Python script reads the outputs of the simulated cards, computes how the plant responds and sets the inputs accordingly, typically every 50 ms and in engineering units. One model can simulate the plant of a whole project across systems, and it can also act as the operator or the DCS over Modbus TCP.
The process model window is generated from what the model declares: its signals with a trend, its parameters, plant faults such as a stuck valve, and one-shot actions. Pause freezes the plant, and Step advances it one step at a time.
The model editor completes the tags of the project’s channels and shows their units and live values. It checks the script as you type and offers fixes, such as the nearest existing tag.
The simulators serve the HMI and the DCS as the controllers do, through the Modbus TCP server and the Modbus TCP I/O service. GA TurWin 4.0.0 or later, started in loopback mode, runs the unchanged RUN file of the plant against the simulators – for operator training on the real screens or to test the screens before commissioning. A DCS reaches the simulators from its own PC at the project addresses; if no DCS is available, BlueSimul Communication simulates it as an external master.
Before a plant is commissioned, every signal is checked from the field terminal to the place where it is displayed or used. On a physical test rack this takes a day of turning potentiometers per system. The simulated loop check does the same with the simulators, signal by signal, against the I/O list, the Modbus lists and the TurWin RUN file:
Note: the simulated loop check is a service of GEBHARDT Automation and not part of the BlueSimul product. It proves that the program, the HMI configuration and the DCS interface agree with the documents; the field wiring is still verified by the physical loop check.
BlueSimul runs the same runtime and the same programs as the controllers on site, so what it shows about the application also holds on site: logic, sequences, limits, voting, switchovers and communication tables. It does not prove the hardware and wiring, the timing of the controller, the plant beyond its model, or the plant network. The loop check and commissioning on site are still required, but with far fewer surprises.
| Operating system | Windows 10 or 11, 64 bit |
|---|---|
| License | CryptoBox with the BlueSimul license, plus the BlueDatalog license for a project with a SoftSPS |
| Engineering | GA BlueEdit 03.23.00 or later, the first version with Loopback mode built in |
| HMI | GA TurWin 4.0.0 or later, the first version with Loopback mode built in |
| Process models | Python 3.10 or later with its standard library |
| Installation | Unpack the archive and install the Microsoft Visual C++ runtime (x86); no setup program, and no administrator rights in loopback mode |
For a demonstration with your own project or for training, please get in touch.