BlueLine³
GA BlueLine³ TMR /LD
Distributed triple redundancy for uninterrupted operation
Three large units with up to 18 cards each work as a spatially distributed TMR system. Full SIL3 safety is maintained even if components fail. The distributed layout avoids common-cause failures.
Architecture
Technical data
| Architecture | three BASIC /L units, triplex architecture |
|---|---|
| Card slots | up to 18 cards (I/O including CPU) plus an FSx switch per unit |
| Backplane bus | Per unit: FS1 bus with 18 slots and integrated Ethernet |
| Mounting | swing frame from the front (19″) |
| Power supply | single or redundant, 24 VDC or 110/230 VAC, rear-mountable, max. 300 W |
| Connections | mainly I/O cards with front-side 50-pin D-Sub sockets |
| Ventilation | front-side circulating fan with fan monitoring; rear dust filter |
| Operating temperature | 0 °C to 60 °C |
| Dimensions | 191 × 483 × 351 mm (H × W × D) |
| Relevant standards | IEC 61508, EN ISO 13849, IEC 62061, EN 61010, IEC 61131, EN 61373 |
Questions about this product?
Our project engineers are happy to advise you on selection and dimensioning.