SIL3 TMR machine control
TMR for Protection and Control
Avoid downtime. Secure production. Triple redundant machine control for critical turbines and compressors.
More availability. Fewer unplanned shutdowns.
The TMR system is triple redundant. This strengthens operational availability and can reduce production losses and restart losses.
SIL3 diagnostics and comparison of the TMR paths reveal hidden faults. Majority decisions and input voting can exclude individual faulty path or sensor values. Most components can be replaced during operation, where continued operation is permitted.
TMR = Triple Modular Redundancy

Increased robustness
Designed for increased environmental resilience
The SIL3 systems were designed from the outset to withstand increased environmental stress. Their tolerance at higher limits for EMC disturbances, temperature stress and enclosure vibration has been demonstrated. They are therefore less susceptible to disturbances than systems designed only for standard limits.
For critical turbines and compressors
Detect and manage faults
The TMR system combines speed, anti-surge, pressure and flow control with protection functions in a fault-tolerant architecture.
Know sooner what is happening
SIL3 diagnostics and path comparison reveal hidden faults. Your team can respond in a targeted way before a fault has an unnoticed effect.
Continue through sensor faults
A detected faulty measurement can be excluded. A configurable degradation strategy uses the remaining valid values where the application permits it.
Maintain during operation
Most components can be replaced during operation. Short repair times help restore full redundancy quickly.
Mid-of-3 examples
Mid-of-3, Min/Max and Average are available for analog inputs. Signal selection depends on the protection or control task.
Mid-of-3 always selects the middle measurement. Example 1: sensor C reads too high (160 bar) – 101 bar is selected. Example 2: sensor A reads too low (40 bar) – 100 bar is selected. In both cases the deviating value is disregarded.
| Example | Sensor A | Sensor B | Sensor C | Selected |
|---|---|---|---|---|
| 1 | 100 bar | 101 bar | 160 bar | 101 bar |
| 2 | 40 bar | 100 bar | 101 bar | 100 bar |
A majority decision can override one deviating path. In a hazardous condition, the intended protective response remains decisive.
The third path advantage
Keep operating and repair during operation
After a detected path failure, the system isolates the affected path and switches to the remaining paths. Two paths remain for operation and repair. In a suitably designed 3–2–1–0 architecture, the function may continue down to one remaining path.
| Situation | SIMPLEX and DUPLEX | TMR |
|---|---|---|
| Value selection | SIMPLEX has no external comparison path; DUPLEX has no majority. | Three paths enable a majority decision. |
| One detected path failure | SIMPLEX loses the function. DUPLEX can continue on one path with suitable switching. | Two paths remain for operation and repair. |
| Two detected path failures | DUPLEX has no functioning path left. | 3–2–1–0 can allow operation on one remaining path. |
| Repair during operation | After the first path failure, DUPLEX has no additional external path reserve. | Two paths remain after the first path failure. |

Short repair times
Most components can be replaced during operation. Fast restoration reduces time spent with diminished redundancy. Spare parts and short service routes help.
Assess the economic value
Avoided unplanned shutdowns can reduce lost production, restart losses and repair costs. The total cost of a plant outage is decisive.
API 670 and asset losses
Account for the full loss
API 670 addresses machinery protection systems. The “asset losses” approach evaluates the economic effects of shutdowns and machinery damage.
During a shutdown
Lost production during the interruption, plus losses of feedstock and during restart.
Additional machinery damage
Spare parts, repair personnel and further lost production during procurement, waiting and repair.
Asset losses risk graph
Severity S, avoidability AV and event frequency W determine the classification. This matrix shows the decision paths of the risk graph.
| Severity | AV | W3 | W2 | W1 | W0 | W−1 | W−2 |
|---|---|---|---|---|---|---|---|
| S1 | – | a | – | – | – | – | – |
| S2 | AV1 | 1 | a | – | – | – | – |
| S2 | AV2 | 2 | 1 | a | – | – | – |
| S3 | AV1 | 2 | 1 | a | – | – | – |
| S3 | AV2 | 3 | 2 | 1 | a | – | – |
| S4 | AV1 | 3 | 2 | 1 | a | – | – |
| S4 | AV2 | 4 | 3 | 2 | 1 | – | – |
S1 minor · S2 moderate · S3 severe · S4 catastrophic. AV1: probability of damage per event ≤ 10%; AV2: > 10%. W3: more than one event per year; frequency decreases toward W−2. 1–4: target SIL classes in the graph; a: no special requirements; –: no requirements according to the graph.
Example: S3 + AV2 + W3 leads to class 3 in the graph shown. Diagnostics, voting and permitted continued operation can reduce unnecessary shutdowns and faulty control actions.
Typical TMR system
One system for multiple machinery functions
An example for a turbine-driven process gas compressor combines speed, anti-surge and pressure control with additional control loops, logic functions and SIL3 signals.

| Control functions | Signals and communication |
|---|---|
| Speed, anti-surge and pressure control 5 additional control loops 8 logic functions | 32 × 3 analog SIL3 inputs 48 × 3 binary SIL3 alarm inputs 10 × 3 binary SIL3 outputs 8 × 3 analog SIL3 outputs Redundant Ethernet ports |
Usable I/O capacity depends on the installed cards, output voters and architecture.
Compact and expandable
A complete system in one 19-inch rack, expandable for additional I/O.
Certified components
Input and output cards and CPUs are SIL3 certified. Hardware and firmware support protection functions up to SIL3.
Machinery practice
API 670 compliant applications, event recording and fast data logging. Triple sensing is recommended for input voting with three measured values.
- Control, regulation and sequencing for multiple machines and control loops in one system.
- Functions for protecting people and the environment where IEC 61508 and IEC 61511 permit them for the application.
- Event recorder and fast data logger in the range below 100 ms.
- Hundreds of references on compressors and turbines.
- Triple sensing is recommended, but is not mandatory for every application.
- Electrical safety is part of the equipment assessment.
Plan protection and control for your plant
We can review the required functions, permitted fault response and suitable TMR architecture for your turbine or compressor.
Get in touch