SIL3 TMR machine control

TMR for Protection and Control

Avoid downtime. Secure production. Triple redundant machine control for critical turbines and compressors.

More availability. Fewer unplanned shutdowns.

The TMR system is triple redundant. This strengthens operational availability and can reduce production losses and restart losses.

SIL3 diagnostics and comparison of the TMR paths reveal hidden faults. Majority decisions and input voting can exclude individual faulty path or sensor values. Most components can be replaced during operation, where continued operation is permitted.

TMR = Triple Modular Redundancy

BlueLine³ GA TMR/CI system
BlueLine³ GA TMR/CI

Increased robustness

Designed for increased environmental resilience

The SIL3 systems were designed from the outset to withstand increased environmental stress. Their tolerance at higher limits for EMC disturbances, temperature stress and enclosure vibration has been demonstrated. They are therefore less susceptible to disturbances than systems designed only for standard limits.

For critical turbines and compressors

Detect and manage faults

The TMR system combines speed, anti-surge, pressure and flow control with protection functions in a fault-tolerant architecture.

Know sooner what is happening

SIL3 diagnostics and path comparison reveal hidden faults. Your team can respond in a targeted way before a fault has an unnoticed effect.

Continue through sensor faults

A detected faulty measurement can be excluded. A configurable degradation strategy uses the remaining valid values where the application permits it.

Maintain during operation

Most components can be replaced during operation. Short repair times help restore full redundancy quickly.

Mid-of-3 examples

Mid-of-3, Min/Max and Average are available for analog inputs. Signal selection depends on the protection or control task.

Mid-of-3 always selects the middle measurement. Example 1: sensor C reads too high (160 bar) – 101 bar is selected. Example 2: sensor A reads too low (40 bar) – 100 bar is selected. In both cases the deviating value is disregarded.

Measurements and selected value in the Mid-of-3 examples
ExampleSensor ASensor BSensor CSelected
1100 bar101 bar160 bar101 bar
240 bar100 bar101 bar100 bar

A majority decision can override one deviating path. In a hazardous condition, the intended protective response remains decisive.

The third path advantage

Keep operating and repair during operation

After a detected path failure, the system isolates the affected path and switches to the remaining paths. Two paths remain for operation and repair. In a suitably designed 3–2–1–0 architecture, the function may continue down to one remaining path.

Comparison of SIMPLEX, DUPLEX and TMR
SituationSIMPLEX and DUPLEXTMR
Value selectionSIMPLEX has no external comparison path; DUPLEX has no majority.Three paths enable a majority decision.
One detected path failureSIMPLEX loses the function. DUPLEX can continue on one path with suitable switching.Two paths remain for operation and repair.
Two detected path failuresDUPLEX has no functioning path left.3–2–1–0 can allow operation on one remaining path.
Repair during operationAfter the first path failure, DUPLEX has no additional external path reserve.Two paths remain after the first path failure.
Three paths degrade to two, then one, before reaching the safe state
The permitted operating strategy depends on the application and its allowable fault response.

Short repair times

Most components can be replaced during operation. Fast restoration reduces time spent with diminished redundancy. Spare parts and short service routes help.

Assess the economic value

Avoided unplanned shutdowns can reduce lost production, restart losses and repair costs. The total cost of a plant outage is decisive.

API 670 and asset losses

Account for the full loss

API 670 addresses machinery protection systems. The “asset losses” approach evaluates the economic effects of shutdowns and machinery damage.

During a shutdown

Lost production during the interruption, plus losses of feedstock and during restart.

Additional machinery damage

Spare parts, repair personnel and further lost production during procurement, waiting and repair.

Asset losses risk graph

Severity S, avoidability AV and event frequency W determine the classification. This matrix shows the decision paths of the risk graph.

Risk graph by severity, avoidability and event frequency
SeverityAVW3W2W1W0W−1W−2
S1–a–––––
S2AV11a––––
S2AV221a–––
S3AV121a–––
S3AV2321a––
S4AV1321a––
S4AV24321––

S1 minor · S2 moderate · S3 severe · S4 catastrophic. AV1: probability of damage per event ≤ 10%; AV2: > 10%. W3: more than one event per year; frequency decreases toward W−2. 1–4: target SIL classes in the graph; a: no special requirements; –: no requirements according to the graph.

Example: S3 + AV2 + W3 leads to class 3 in the graph shown. Diagnostics, voting and permitted continued operation can reduce unnecessary shutdowns and faulty control actions.

Typical TMR system

One system for multiple machinery functions

An example for a turbine-driven process gas compressor combines speed, anti-surge and pressure control with additional control loops, logic functions and SIL3 signals.

Front view of the BlueLine³ GA TMR/CI rack
BlueLine³ GA TMR/CI
Example configuration for a turbine-driven process gas compressor
Control functionsSignals and communication
Speed, anti-surge and pressure control
5 additional control loops
8 logic functions
32 × 3 analog SIL3 inputs
48 × 3 binary SIL3 alarm inputs
10 × 3 binary SIL3 outputs
8 × 3 analog SIL3 outputs
Redundant Ethernet ports

Usable I/O capacity depends on the installed cards, output voters and architecture.

Compact and expandable

A complete system in one 19-inch rack, expandable for additional I/O.

Certified components

Input and output cards and CPUs are SIL3 certified. Hardware and firmware support protection functions up to SIL3.

Machinery practice

API 670 compliant applications, event recording and fast data logging. Triple sensing is recommended for input voting with three measured values.

  • Control, regulation and sequencing for multiple machines and control loops in one system.
  • Functions for protecting people and the environment where IEC 61508 and IEC 61511 permit them for the application.
  • Event recorder and fast data logger in the range below 100 ms.
  • Hundreds of references on compressors and turbines.
  • Triple sensing is recommended, but is not mandatory for every application.
  • Electrical safety is part of the equipment assessment.

Plan protection and control for your plant

We can review the required functions, permitted fault response and suitable TMR architecture for your turbine or compressor.

Get in touch