GA BlueLine² TMR /LD

Distributed triple redundancy for fail-safe operation

The GA BlueLine2 TMR /LD is set up for maximum safety at maximum availability. Three independent units, each with up to 18 I/O cards (incl. CPU), operate as a logical TMR system with triple modular redundancy. Even in the event of a component failure the system continues to work with full SIL3 safety. All components can be hot-swapped during operation.

The separation of the redundant TMR unit into independent racks simplifies the connection of field signals, improves climatic conditions and improves the reliability (keyword "common cause failure").

Housed in compact 19” racks, it is perfectly suited for mounting in a swing frame.

Technical Specification

  • Architecture: three identical BASIC /L units, configured as logical TMR architecture
  • Racks each for up to 18 cards (I/O cards including CPU) plus FSx switch
  • Data bus: FS1 bus with integrated Ethernet
  • Assembly: swing frame (19“)
  • Power supply: single or redundant 24VDC or 110/230VAC, rear installation, max. 300W

 

  • Connectors: primarily I/O cards with frontal 50-pin D-sub socket
  • Ventilation: built-in active fan, replaceable from front, with fan monitoring
  • replaceable dirt filter under the rack, replaceable from rear

 

  • Operating temperature range: 0° ... +60°C (+32° ... 140°F)
  • Dimensions: 191 x 483 x 351 mm (H x W x D)
  • Standards: IEC 61508, EN ISO 13849, IEC 62061, IEC 61511, IEC 61131, EN 50178